MACX MCR-EX-SL-RPSSI-2I-SP 数据手册
https://www.phoenixcontact.com/us/products/2924236
Repeater power supply - MACX MCR-EX-SL-RPSSI-2I-SP - 2924236
Please be informed that the data shown in this PDF Document is generated from our Online Catalog. Please find the complete data in the user's
documentation. Our General Terms of Use for Downloads are valid
(http://phoenixcontact.com/download)
Ex i measuring transducer power supply and input isolating amplifier, HART. Transfers supplied or active 0/4 20 mA electrically isolated signals from the Ex area to two loads in the safe area. 4-way electrical isolation, SIL 2
according to IEC 61508, push-in Technology.
Product description
Repeater power supply and input isolating amplifier for the operation of intrinsically safe (Ex-i) 2-wire measuring transducers, 4-wire measuring
transducers, and mA current sources installed in Ex areas.
– 0/4 ... 20 mA, [Ex ia] IIC input (powered or not powered)
– Two electrically isolated 0/4 ... 20 mA (active) outputs
- Bidirectional transmission of digital HART communication signals (both outputs)
– Plug-in screw or spring-cage connection method, with integrated sockets for HART communicators
- 4-way electrical isolation
- Energy can be supplied via DIN rail connector
- Up to SIL 2 according to EN 61508
- Installation in zone 2, protection type "n" (EN 60079-15) permitted
Product Features
Power supply possible via DIN rail connector
Up to SIL 2 according to EN 61508
Installation in zone 2, protection type "n" (EN 60079-15) permitted
0/4 ... 20 mA input, [Ex ia] IIC (powered or not powered)
Two electrically isolated 0/4 ... 20 mA (active) outputs
Bidirectional transmission of digital HART communication signals (both outputs)
Plug-in screw or spring-cage connection technology (Push-in technology), with integrated sockets for HART communicators
4-way electrical isolation
Key commercial data
Packing unit
1 pc
Weight per Piece (excluding packing)
160.0 GRM
Custom tariff number
85437090
Country of origin
Germany
10/10/2014 Page 1 / 7
https://www.phoenixcontact.com/us/products/2924236
Repeater power supply - MACX MCR-EX-SL-RPSSI-2I-SP - 2924236
Technical data
Note
Utilization restriction
EMC: class A product, see manufacturer's declaration in the download
area
Dimensions
Width
12.5 mm
Height
99 mm
Depth
114.5 mm
Ambient conditions
Ambient temperature (operation)
-20 °C ... 60 °C (Any mounting position)
Ambient temperature (storage/transport)
-40 °C ... 80 °C
Maximum altitude
≤ 2000 m
Permissible humidity (operation)
10 % ... 95 % (non-condensing)
Degree of protection
IP20
Input data
Signal input
Repeater power supply operation
Current input signal
4 mA ... 20 mA
Transmitter supply voltage
> 16 V (at 20 mA)
> 15.1 V (at 23 mA)
Signal input
Signal conditioner operation
Current input signal
0 A ... 20 mA
4 mA ... 20 mA
Voltage drop
approx. 3.9 V
Output data
Signal output
Repeater power supply operation
Current output signal
4 mA ... 20 mA (active)
Load/output load current output
< 450 Ω (at 20 mA)
< 380 Ω (at 23 mA)
Output ripple
< 20 mVrms
Output behavior in the event of an error
0 mA (Cable break in the input)
≥ 23 mA (Cable short-circuit in the input)
Signal output
Signal conditioner operation
Current output signal
0 mA ... 20 mA (active)
4 mA ... 20 mA (active)
Load/output load current output
< 450 Ω (at 20 mA)
< 380 Ω (at 23 mA)
Output ripple
< 20 mVrms
10/10/2014 Page 2 / 7
https://www.phoenixcontact.com/us/products/2924236
Repeater power supply - MACX MCR-EX-SL-RPSSI-2I-SP - 2924236
Technical data
Output data
Output behavior in the event of an error
0 mA (Cable break in the input)
0 mA (Cable short-circuit in the input)
Power supply
Supply voltage range
19.2 V DC ... 30 V DC (24 V DC (-20% ... +25%))
Max. current consumption
< 75 mA (24 V DC/ 20 mA)
Power consumption
< 1.45 W (24 V DC/ 20 mA)
Connection data
Conductor cross section solid min.
0.2 mm²
Conductor cross section solid max.
1.5 mm²
Conductor cross section stranded min.
0.2 mm²
Conductor cross section stranded max.
1.5 mm²
Conductor cross section AWG/kcmil min.
24
Conductor cross section AWG/kcmil max
16
Stripping length
8 mm
Connection method
Spring-cage connection
General
Maximum transmission error
< 0.1 % (of final value)
Transmission error, typical
< 0.05 % (of final value)
Maximum temperature coefficient
< 0.01 %/K
Step response (10-90%)
< 600 µs (for 4 mA ... 20 mA step)
Status display
Green LED (PWR supply voltage)
Inflammability class according to UL 94
V0
Housing material
PA 66-FR
Color
green
Designation
Input/output/power supply
Electrical isolation
300 Vrms (Rated insulation voltage (surge voltage category II; pollution
degree 2, safe isolation as per EN 61010-1))
2.5 kV (50 Hz, 1 min., test voltage)
Designation
Input/output
Electrical isolation
375 V (Peak value in accordance with EN 60079-11)
Designation
Input/power supply
Electrical isolation
375 V (Peak value in accordance with EN 60079-11)
Designation
Output 1/output 2
Electrical isolation
1.5 kV AC (50 Hz, 1 min., test voltage)
Conformance
CE-compliant, additionally EN 61326
ATEX
II (1) G [Ex ia Ga] IIC/IIB
10/10/2014 Page 3 / 7
https://www.phoenixcontact.com/us/products/2924236
Repeater power supply - MACX MCR-EX-SL-RPSSI-2I-SP - 2924236
Technical data
General
II (1) D [Ex ia Da] IIIC
II 3 (1) G Ex nA [ia Ga] IIC/IIB T4 Gc
IECEx
[Ex ia Ga] IIC/IIB
[Ex ia Da] IIIC
Ex nA [ia Ga] IIC/IIB T4 Gc
Functional Safety (SIL)
SIL 2 according to EN 61508
Data communication (bypass)
HART function
Yes
Protocols supported
HART
Safety data
Operation
Repeater power supply operation
Max. output voltage Uo
25.2 V
Max. output current Io
93 mA
Max. output power Po
587 mW
Group
IIC
Max. external inductivity Lo
2 mH
Max. external capacity Co
107 nF
Group
IIB
Max. external inductivity Lo
4 mH
Max. external capacity Co
820 nF
Safety-related maximum voltage Um
253 V AC (125 V DC)
Operation
Signal conditioner operation
Input voltage Ui
≤ 30 V
Input current Ii
≤ 150 mA
Max. internal inductance Li
negligible
Max. internal capacitance Ci
negligible
Classifications
eCl@ss
eCl@ss 4.0
27210120
eCl@ss 4.1
27210120
eCl@ss 5.0
27210120
eCl@ss 5.1
27210120
eCl@ss 6.0
27210120
eCl@ss 7.0
27210120
10/10/2014 Page 4 / 7
https://www.phoenixcontact.com/us/products/2924236
Repeater power supply - MACX MCR-EX-SL-RPSSI-2I-SP - 2924236
Classifications
eCl@ss
eCl@ss 8.0
27210120
ETIM
ETIM 2.0
EC001485
ETIM 3.0
EC001485
ETIM 4.0
EC001485
ETIM 5.0
EC002653
UNSPSC
UNSPSC 6.01
30211506
UNSPSC 7.0901
39121008
UNSPSC 11
39121008
UNSPSC 12.01
39121008
UNSPSC 13.2
39121008
Approvals
Approvals
Approvals
Functional Safety / UL Listed / cUL Listed / cUL Listed / cULus Listed / cULus Listed / cULus Listed / null / null / null / null
Ex Approvals
IECEx / ATEX
Approvals submitted
Approval details
Functional Safety
UL Listed
10/10/2014 Page 5 / 7
https://www.phoenixcontact.com/us/products/2924236
Repeater power supply - MACX MCR-EX-SL-RPSSI-2I-SP - 2924236
Approvals
cUL Listed
cUL Listed
cULus Listed
cULus Listed
cULus Listed
Drawings
10/10/2014 Page 6 / 7
https://www.phoenixcontact.com/us/products/2924236
Repeater power supply - MACX MCR-EX-SL-RPSSI-2I-SP - 2924236
Block diagram
OUT
IN
Sensor / Field
PLC / DCS
AI
passive
4.2 - 4.2
4.1
+
3.2
3.2
OUT 1
4.1
3.1
or
3.1
+
2.2
passive
OUT 2
2.1
5.2 - 5.2
5.1
+
GND
5.1
+24V
1.2
2.2
2.1
+
1.1
Power
GND +24V
Zone 0,1,2
Zone 20,21,22
Zone 2
Div. 1,2
Div. 2
Phoenix Contact 2014 © - all rights reserved
http://www.phoenixcontact.com
10/10/2014 Page 7 / 7